FLUKE 319 CLAMP METERS

FLUKE 319 Clamp Meters

The Fluke 319 Clamp Meter is an essential tool for electricians and technicians, offering high-precision measurement in a compact, portable design. It features a unique 40A low-current measurement with 0.01A resolution and 1.6% accuracy, making it ideal for diagnosing sensitive electrical systems. Its slim, lightweight clamps are perfect for confined spaces, while the large, backlit display ensures easy readability in dark environments. With advanced functions like starting current (inrush) measurement, current frequency measurement, and a screen hold function, the Fluke 319 provides comprehensive capabilities for a wide range of applications. The meter also includes a continuity beeper and an auto-off function to conserve battery life, making it a reliable and convenient tool backed by a one-year warranty.

  • Unique 40A high-precision low current measurement–0.01A high-resolution, 1.6% high-precision measurement
  • The clamps are slim, lightweight, and portable, making them ideal for use in small, confined spaces
  • The large backlight display facilitates readings in dark environments
  • Starting current (inrush) functionality (319) allows measurement of the starting current of electrical and lighting equipment, for example. (319)
  • Current frequency measurement
  • Precision down to 0.01A and 0.1V
  • 1000A/600A AC/DC current measurement (319/317)
  • 600V AC/DC voltage measurement
  • 4000Ω resistance measurement
  • Continuity beeper
  • Auto off function enhances battery life, meaning the instrument can work when you need it screen store ‘hold’ function for capturing a measurement result on the screen
  • One year warranty

 

Specifications Of FLUKE 319 Clamp Meters

General specifications

Digital display

6000 count resolution

Low battery Indication

Displays a signal when the batteries are below their required voltage

Power source

Three AAA IEC LR03 batteries

Clamp opening size

1.45 in (37 mm)

Jaw diameter

1.45 in (37 mm)

Dimensions (L x W x H)

9.21 in x 2.95 in x 1.37 in

(234.0 mm x 75.0 mm x 34.8 mm)

Weight

Approximately 13.5 oz (384 g) (batteries included)

Auto range

Available in Ohms

Safety

CE

EN/IEC 61010-1 and IEC 61010-2-032

Measurement Category: 600V CAT III

317 Electrical specifications

Current AC

Range

40.00 A, 600.0 A

Resolution

0.01 A, 0.1 A

Accuracy

1.6% ±6 digit (50-60 Hz) {40 A}

2.5% ±8 digit (60-500 Hz) {40 A}

1.5% ±5 digit (50-60 Hz) {600 A}

2.5% ±5 digit (60-500 Hz) {600 A}

Crest Factor add 2% into spec for CF > 2

3.0 Max @ 500 A, 2.5 Max @ 600 A

AC response

rms

Current DC

Range

40.00 A, 600.0 A

Resolution

0.01 A, 0.1 A

Accuracy

1.6% ±6 digit (40 A)

1.5% ±5 digit (600 A)

Voltage AC

Range

600.0 V

Resolution

0.1 V

Accuracy

1.5% ±5 digit (20-500Hz)

AC response

rms

Voltage DC

Range

600.0 V

Resolution

0.1 V

Accuracy

1% ±4 digit

Resistance

Range

400.0 Ω, 4000 Ω

Resolution

0.1 Ω, 1 Ω

Accuracy

1% ±5 digit

Continuity

≤ 30 Ω

Inrush

Integration time

N/A

Frequency

Range

N/A

Accuracy

N/A

Trigger Level

N/A

319 Electrical specifications

Current AC

Range

40.00 A, 600.0 A, 1000 A

Resolution

0.01 A, 0.1 A, 1 A

Accuracy

1.6% ±6 digit (50-60 Hz) {40 A}

2.5% ±8 digit (60-500 Hz) {40 A}

1.5% ±5 digit (50-60 Hz) {600/1000 A}

2.5% ±5 digit (60-500 Hz) {600/1000 A}

Crest Factor add 2% into spec for CF > 2

3.0 Max @ 500 A, 2.5 Max @ 600 A, 1.4 Max @ 1000 A

AC response

rms

Current DC

Range

40.00 A, 600.0 A, 1000 A

Resolution

0.01 A, 0.1 A, 1 A

Accuracy

1.6% ±6 digit (40 A)

1.5% ±5 digit (600/1000 A)

Voltage AC

Range

600.0 V

Resolution

0.1 V

Accuracy

1.5% ±5 digit (20-500Hz)

AC response

rms

Voltage DC

Range

600.0 V

Resolution

0.1 V

Accuracy

1% ±4 digit

Resistance

Range

400.0 Ω

4000 Ω

Resolution

0.1 Ω

1 Ω

Accuracy

1% ±5 digit

Continuity

≤ 30 Ω

Inrush

Integration time

100 ms

Frequency

Range

5.0 – 500.0 Hz

Accuracy

0.5% ±5 digit

Trigger Level

10 – 100 Hz ≥ 5 A, 5 – 10 Hz, 100 – 500 Hz ≥ 10 A

The accuracy specifications aply at 73 °F ±41 °F (23 °C ±5 °C)

Below 64 °F and above 82 °F (18 °C and above 28 °C) accuracy degrades at (0.1) times specification per °C.

True rms for ac V and ac A accuracy is specified from 5% to 100% of range.

Environmental specifications

Operating temperature

14°F to 122°F (-10 °C to 50 °C)

Storage temperature

-40 °F to 140 °F (-40 °C to 60 °C)

Operating humidity

Non-condensing (< 50 °F) (< 10 °C)

90% RH (50 °F to 86 °F) (10 °C to 30 °C)

75% RH (86 °F to 104 °F) (30 °C to 40 °C)

45% RH (104 °F to 122 °F) (40 °C to 50 °C)

(Without condensation)

Operating altitude

1 mile (2000 meters) above mean sea level

Storage altitude

7 miles (12,000 meters) above mean sea level

IP Rating

IP40

Vibration requirements

Random MIL-PRF-28800F Class 2, 5-500 Hz, 30 minutes per axis

Drop test requirements

3 ft (1 m) drop test, six sides, oak floor

EMI, RFI, EMC

Instrument unspecified for use in EMC field ≥ 0.1 V/m

Temperature coefficients

0.1x (specified accuracy)/ °C

(<64 °F or > 82° F)

(<18 °C or > 28 °C)